Benutzer-Werkzeuge

Webseiten-Werkzeuge


opc-ua_en

Unterschiede

Hier werden die Unterschiede zwischen zwei Versionen gezeigt.

Link zu der Vergleichsansicht

Beide Seiten, vorherige Überarbeitung Vorherige Überarbeitung
Nächste Überarbeitung
Vorherige Überarbeitung
opc-ua_en [05.12.2019 14:46]
sdi
opc-ua_en [21.03.2021 17:34] (aktuell)
oni
Zeile 16: Zeile 16:
 ^  X  |Floating point value (with decimal place) which can/shall only be read by the gateway  | ^  X  |Floating point value (with decimal place) which can/shall only be read by the gateway  |
 ^  Y  |Floating point value (with decimal place) which can be either read or written by the gateway. | ^  Y  |Floating point value (with decimal place) which can be either read or written by the gateway. |
 +^  A  |String is used e.g. in BACnet Trends and ESPA 4.4.4 data points  |
  
 The OPC-UA addresses are defined as follows:\\ The OPC-UA addresses are defined as follows:\\
Zeile 24: Zeile 25:
 ^modifier |M, S, X, Y (Sets the OPC-UA AccessLevel for the datapoint/node) | ^modifier |M, S, X, Y (Sets the OPC-UA AccessLevel for the datapoint/node) |
 ^system |Directs the driver to act either as Server (Srv) or as Client (Cli) | ^system |Directs the driver to act either as Server (Srv) or as Client (Cli) |
-^NodeId |Typical OPC-UA NodeId, terminated with an semicolon (';')\\ The Namespace (ns) is part of an NodeId. When it's omitted, the ns will point\\to Namepsace 0 (defined by %%http://opcfoundation.org/UA/%%).\\ This namespace includes predefined addresses of OPCFoundation. To avoid conflicts it is recommended to use ns=1 or ns=2! \\ ns=1 : Namespace-Index 1, already defined by opcua configuration parameter ApplicationUri \\ ns=2 : Namespace-Index 2, optional and needs to be defined by opcua configuration parameter Namespace\\ \\ i=numeric (z.B.: ns=1;i=4711;)\\ s=string (z.B.: ns=1;s=current-time;)\\ g=guid (z.B.: ns=1;g=C496578A-0DFE-4b8f-870A-745238C6AEAE;) \\ \\ Bytestring (b) is currently not supported. |+^NodeId |Typical OPC-UA NodeId, terminated with semicolon (';')\\ The Namespace (ns) is part of an NodeId. When it's omitted, the ns will point\\to Namepsace 0 (defined by %%http://opcfoundation.org/UA/%%).\\ This namespace includes predefined addresses of OPCFoundation. To avoid conflicts it is recommended to use ns=1 or ns=2! \\ ns=1 : Namespace-Index 1, already defined by opcua configuration parameter ApplicationUri \\ ns=2 : Namespace-Index 2, optional and needs to be defined by opcua configuration parameter Namespace\\ \\ i=numeric (z.B.: ns=1;i=4711;)\\ s=string (z.B.: ns=1;s=current-time;)\\ g=guid (z.B.: ns=1;g=C496578A-0DFE-4b8f-870A-745238C6AEAE;) \\ \\ Bytestring (b) is currently not supported. |
 ^specialType |Optional: Reserved for special types like the Failure-Datapoint (failure) or the BadTime-Indication-Datapoint (badtime).\\ \\ All special types are and should be read-only! | ^specialType |Optional: Reserved for special types like the Failure-Datapoint (failure) or the BadTime-Indication-Datapoint (badtime).\\ \\ All special types are and should be read-only! |
 \\ \\
Zeile 50: Zeile 51:
  
 === Examples === === Examples ===
 +  [A Srv ns=1; i=9;]
 +  name = Timestamp
 +  format = STRING
 +  
   [M Cli i=4712;]   [M Cli i=4712;]
   name = Client1 Datapoint (readonly) on namespace 0 index 4712   name = Client1 Datapoint (readonly) on namespace 0 index 4712
Zeile 58: Zeile 63:
   format = UINT16   format = UINT16
      
-  [M Cli ns=1;i=4710; failure]+  [M Cli ns=1; i=4710; failure]
   name = Cl1 Failure-Datapoint on namespace 1 index 4710   name = Cl1 Failure-Datapoint on namespace 1 index 4710
   format = SINT32   format = SINT32
        
-  [M Cli ns=1;s=FailureTime; badtime]+  [M Cli ns=1; s=FailureTime; badtime]
   name = Client 1 Time-Failure-Datapoint on namespace 1 by name "FailureTime"   name = Client 1 Time-Failure-Datapoint on namespace 1 by name "FailureTime"
   format = SINT32   format = SINT32
        
-  [X Cli ns=2;s={Device,201};{BinaryInput,4016};PresentValue;]+  [X Cli ns=2; s={Device,201};{BinaryInput,4016};PresentValue;]
   name = Client-2 BI-4016   name = Client-2 BI-4016
   format = FLOAT64   format = FLOAT64
        
-  [Y Srv ns=1;s=some_value;]+  [Y Srv ns=1; s=some_value;]
   name = Server Datapoint (read-/writeable) on namespace 1 by name "some_value"   name = Server Datapoint (read-/writeable) on namespace 1 by name "some_value"
   format = FLOAT32   format = FLOAT32
-  displayname = Server Datapoint 'some_value' +  ua_displayname = Server Datapoint 'some_value' 
-  description = another dp+  ua_description = another dp
      
   [Y Srv ns=1;g=C496578A-0DFE-4b8f-870A-745238C6AEAE;]   [Y Srv ns=1;g=C496578A-0DFE-4b8f-870A-745238C6AEAE;]
Zeile 126: Zeile 131:
 ^::: |Password |"" |string | |password for login (or empty), mandatory if UserTokenType = username | ^::: |Password |"" |string | |password for login (or empty), mandatory if UserTokenType = username |
  
 +<sub>[[https://www.mbs-solutions.de/impressum|Imprint/Impressum]]
 +[[https://www.mbs-solutions.de/disclaimer|Disclaimer]]
 +[[https://www.mbs-solutions.de/datenschutzerklaerung|DSGVO/Privacy Policy]]</sub>
opc-ua_en.1575557183.txt.gz · Zuletzt geändert: 05.12.2019 14:46 von sdi