 Highlights of the LON-FT Bus-System: Highlights of the LON-FT Bus-System:
 - Free Topology (line and star) - Free Topology (line and star)
-- twisted pair +- twisted pair
 - 78kbit/s - 78kbit/s
 - max 64 clients (LON-Knot) each  bus segment - max 64 clients (LON-Knot) each  bus segment
Zeile 17: Zeile 17:
  
  
-Following data point definitions are valid: +Following data point definitions are valid:
  
 ^Type  ^Description  ^ ^Type  ^Description  ^
Zeile 28: Zeile 28:
 Addresses are defined as follows: Addresses are defined as follows:
  
-**explizit addressing with Neuron-ID**\\  +**explizit addressing with Neuron-ID**\\ 
-<SNVT> <Neuron-ID>.<nr>[/<sub>] [<*|/T <sek>>]+<SNVT> <Neuron-ID>.<nr>[/<sub>] [<*|/T <sec>>] [</H <sec>>]
  
-**explizit addressing with Domain-ID.Subnet.Node**\\  +**explizit addressing with Domain-ID.Subnet.Node**\\ 
-<SNVT-Typ> <Domain-ID>.<Subnet>.<Node>.<nr>[/<sub>] [<*|/T <sek>>]\\ +<SNVT-Typ> <Domain-ID>.<Subnet>.<Node>.<nr>[/<sub>] [<*|/T <sec>>] [</H <sec>>]\\
 Domain-ID always 0. Domain-ID always 0.
  
-**Binding** (requires LON-Binding-Tool e.g. LON-Maker) \\  +**Binding** (requires LON-Binding-Tool e.g. LON-Maker) \\ 
-<SNVT-Typ>  - - -  <nr>[/<sub>] [<*|/T <sek>>]+<SNVT-Typ>  - - -  <nr>[/<sub>] [<*|/T <sec>>] [</H <sec>>]
  
 A maximum of 1024 variables can be provided for binding. A maximum of 1024 variables can be provided for binding.
Zeile 47: Zeile 47:
 ^nr  |sequential number to SNVT within gateway/device| ^nr  |sequential number to SNVT within gateway/device|
 ^sub  |element number within SNVT  | ^sub  |element number within SNVT  |
-^*  |trigger element  |+^*  |trigger element writes directly  |
 ^/T <sec>  |timeout for trigger in <sec>  | ^/T <sec>  |timeout for trigger in <sec>  |
 +^/H <sec>  |Heartbeat for cyclic sending an output variable value every <sec> |
 +
  
 Typical data point definitions: Typical data point definitions:
  
   Addressing with Neuron-ID:   Addressing with Neuron-ID:
-   +
   [X object 1]   [X object 1]
     name = analogue value read by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-No. 4 within a device with Neuron-ID 000360850201     name = analogue value read by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-No. 4 within a device with Neuron-ID 000360850201
     query = pe     query = pe
     format = 66 000360850201.4     format = 66 000360850201.4
-   +
   [X object 2]   [X object 2]
     name = analogue value read by the gateway. SNVT-type 105 (SNVT_temp_p), SNVT-No. 12 within a device with Neuron-ID 000360850201     name = analogue value read by the gateway. SNVT-type 105 (SNVT_temp_p), SNVT-No. 12 within a device with Neuron-ID 000360850201
     query = pe     query = pe
     format = 105 000360850201.12     format = 105 000360850201.12
-   +
   [Y object 3]   [Y object 3]
     name = analogue value written by the gateway. SNVT-type 95 (SNVT_switch[value]), SNVT-No. 4 within the device with Neuron-ID 00A051437401     name = analogue value written by the gateway. SNVT-type 95 (SNVT_switch[value]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
Zeile 69: Zeile 71:
     writecache = yes     writecache = yes
     format = 95 00A051437401.4     format = 95 00A051437401.4
-   +
   [S object 4]   [S object 4]
     name = integer value written by the gateway. SNVT-type 95 (SNVT_switch[state]), SNVT-No. 4 within the device with Neuron-ID 00A051437401     name = integer value written by the gateway. SNVT-type 95 (SNVT_switch[state]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
Zeile 75: Zeile 77:
     writecache = yes     writecache = yes
     format = 95 00A051437401.4     format = 95 00A051437401.4
-   +
   [M object 5]   [M object 5]
     name = binary value read by the gateway. SNVT-type 83 (SNVT_state[Bit16]), SNVT-No. 5 within the device with Neuron-ID 00A051437401     name = binary value read by the gateway. SNVT-type 83 (SNVT_state[Bit16]), SNVT-No. 5 within the device with Neuron-ID 00A051437401
Zeile 81: Zeile 83:
     writecache = yes     writecache = yes
     format = 83 00A051437401.5/1     format = 83 00A051437401.5/1
-   +
   [M object 6]   [M object 6]
     name = binary value written by the gateway. SNVT-type 83 (SNVT_state[Bit15]), SNVT-No. 5 5 within the device with Neuron-ID 00A051437401     name = binary value written by the gateway. SNVT-type 83 (SNVT_state[Bit15]), SNVT-No. 5 5 within the device with Neuron-ID 00A051437401
Zeile 89: Zeile 91:
  
   Addressing with Domain-ID.Subnet.Node:   Addressing with Domain-ID.Subnet.Node:
-    + 
-    [X object 1]+  [X object 1]
     name = analogue value rerd by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-Nr. 4 within the device with address 01.02.03     name = analogue value rerd by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-Nr. 4 within the device with address 01.02.03
     query = pe     query = pe
     format = 66 01.02.03.4     format = 66 01.02.03.4
 +
 +  [X object 2]
 +    name = addressing structural element value. SNVT-Typ 95 (SNVT_switch), SNVT-Nr. 32 within the device with address 00.02.04
 +    query = pe
 +    format = 95 00.02.04.32/1
 +
 +  [X object 3]
 +    name = addressing structural element state. SNVT-Typ 95 (SNVT_switch), SNVT-Nr. 32 within the device with address 00.02.04
 +    query = pe
 +    format = 95 00.02.04.32/2
  
   Adressing with binding:   Adressing with binding:
-    + 
-    [Y object 1]+  [Y object 1]
     name = Analogue value provided by the gateway. SNVT-Typ 66 (SNVT_volt_f), SNVT-Nr. 2 within the gateway     name = Analogue value provided by the gateway. SNVT-Typ 66 (SNVT_volt_f), SNVT-Nr. 2 within the gateway
     query = pe     query = pe
     format = 66 --- 2     format = 66 --- 2
 +
 +
 +Alternatively you can specify the address formats 'Domain-ID.Subnet.Node' and 'Neuron-ID' directly:
 +
 +  [X 66 000360850201.4]
 +    name = analogue value read by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-No. 4 within a device with Neuron-ID 000360850201
 +    query = pe
 +
 +  [X 105 000360850201.12]
 +    name = analogue value read by the gateway. SNVT-type 105 (SNVT_temp_p), SNVT-No. 12 within a device with Neuron-ID 000360850201
 +    query = pe
 +
 +  [Y 95 00A051437401.4]
 +    name = analogue value written by the gateway. SNVT-type 95 (SNVT_switch[value]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [S 95 00A051437401.4]
 +    name = integer value written by the gateway. SNVT-type 95 (SNVT_switch[state]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [M 83 00A051437401.5/1]
 +    name = binary value read by the gateway. SNVT-type 83 (SNVT_state[Bit16]), SNVT-No. 5 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [M 83 00A051437401.5/2]
 +    name = binary value written by the gateway. SNVT-type 83 (SNVT_state[Bit15]), SNVT-No. 5 5 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [X 66 01.02.03.4]
 +    name = analogue value rerd by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-Nr. 4 within the device with address 01.02.03
 +    query = pe
 +
 +  [X 95 00.02.04.32/1]
 +    name = addressing structural element value. SNVT-Typ 95 (SNVT_switch), SNVT-Nr. 32 within the device with address 00.02.04
 +    query = pe
 +
 +  [M 95 00.02.04.32/2]
 +    name = addressing structural element state. SNVT-Typ 95 (SNVT_switch), SNVT-Nr. 32 within the device with address 00.02.04
 +    query = pe
 +