Benutzer-Werkzeuge

Webseiten-Werkzeuge


lon_en

Unterschiede

Hier werden die Unterschiede zwischen zwei Versionen gezeigt.

Link zu der Vergleichsansicht

Beide Seiten, vorherige Überarbeitung Vorherige Überarbeitung
Nächste Überarbeitung
Vorherige Überarbeitung
Letzte Überarbeitung Beide Seiten, nächste Überarbeitung
lon_en [27.10.2017 13:26]
fla
lon_en [20.06.2018 07:20]
amu
Zeile 5: Zeile 5:
 Highlights of the LON-FT Bus-System: Highlights of the LON-FT Bus-System:
 - Free Topology (line and star) - Free Topology (line and star)
-- twisted pair +- twisted pair
 - 78kbit/s - 78kbit/s
 - max 64 clients (LON-Knot) each  bus segment - max 64 clients (LON-Knot) each  bus segment
Zeile 17: Zeile 17:
  
  
-Following data point definitions are valid: +Following data point definitions are valid:
  
 ^Type  ^Description  ^ ^Type  ^Description  ^
Zeile 28: Zeile 28:
 Addresses are defined as follows: Addresses are defined as follows:
  
-**explizit addressing with Neuron-ID**\\  +**explizit addressing with Neuron-ID**\\ 
-<SNVT> <Neuron-ID>.<nr>[/<sub>] [<*|/T <sek>>]+<SNVT> <Neuron-ID>.<nr>[/<sub>] [<*|/T <sec>>] [</H <sec>>]
  
-**explizit addressing with Domain-ID.Subnet.Node**\\  +**explizit addressing with Domain-ID.Subnet.Node**\\ 
-<SNVT-Typ> <Domain-ID>.<Subnet>.<Node>.<nr>[/<sub>] [<*|/T <sek>>]\\ +<SNVT-Typ> <Domain-ID>.<Subnet>.<Node>.<nr>[/<sub>] [<*|/T <sec>>] [</H <sec>>]\\
 Domain-ID always 0. Domain-ID always 0.
  
-**Binding** (requires LON-Binding-Tool e.g. LON-Maker) \\  +**Binding** (requires LON-Binding-Tool e.g. LON-Maker) \\ 
-<SNVT-Typ>  - - -  <nr>[/<sub>] [<*|/T <sek>>]+<SNVT-Typ>  - - -  <nr>[/<sub>] [<*|/T <sec>>] [</H <sec>>]
  
 A maximum of 1024 variables can be provided for binding. A maximum of 1024 variables can be provided for binding.
Zeile 47: Zeile 47:
 ^nr  |sequential number to SNVT within gateway/device| ^nr  |sequential number to SNVT within gateway/device|
 ^sub  |element number within SNVT  | ^sub  |element number within SNVT  |
-^*  |trigger element  |+^*  |trigger element writes directly  |
 ^/T <sec>  |timeout for trigger in <sec>  | ^/T <sec>  |timeout for trigger in <sec>  |
 +^/H <sec>  |Heartbeat for cyclic sending an output variable value every <sec> |
 +
  
 Typical data point definitions: Typical data point definitions:
  
   Addressing with Neuron-ID:   Addressing with Neuron-ID:
-   +
   [X object 1]   [X object 1]
     name = analogue value read by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-No. 4 within a device with Neuron-ID 000360850201     name = analogue value read by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-No. 4 within a device with Neuron-ID 000360850201
     query = pe     query = pe
     format = 66 000360850201.4     format = 66 000360850201.4
-   +
   [X object 2]   [X object 2]
     name = analogue value read by the gateway. SNVT-type 105 (SNVT_temp_p), SNVT-No. 12 within a device with Neuron-ID 000360850201     name = analogue value read by the gateway. SNVT-type 105 (SNVT_temp_p), SNVT-No. 12 within a device with Neuron-ID 000360850201
     query = pe     query = pe
     format = 105 000360850201.12     format = 105 000360850201.12
-   +
   [Y object 3]   [Y object 3]
     name = analogue value written by the gateway. SNVT-type 95 (SNVT_switch[value]), SNVT-No. 4 within the device with Neuron-ID 00A051437401     name = analogue value written by the gateway. SNVT-type 95 (SNVT_switch[value]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
Zeile 69: Zeile 71:
     writecache = yes     writecache = yes
     format = 95 00A051437401.4     format = 95 00A051437401.4
-   +
   [S object 4]   [S object 4]
     name = integer value written by the gateway. SNVT-type 95 (SNVT_switch[state]), SNVT-No. 4 within the device with Neuron-ID 00A051437401     name = integer value written by the gateway. SNVT-type 95 (SNVT_switch[state]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
Zeile 75: Zeile 77:
     writecache = yes     writecache = yes
     format = 95 00A051437401.4     format = 95 00A051437401.4
-   +
   [M object 5]   [M object 5]
     name = binary value read by the gateway. SNVT-type 83 (SNVT_state[Bit16]), SNVT-No. 5 within the device with Neuron-ID 00A051437401     name = binary value read by the gateway. SNVT-type 83 (SNVT_state[Bit16]), SNVT-No. 5 within the device with Neuron-ID 00A051437401
Zeile 81: Zeile 83:
     writecache = yes     writecache = yes
     format = 83 00A051437401.5/1     format = 83 00A051437401.5/1
-   +
   [M object 6]   [M object 6]
     name = binary value written by the gateway. SNVT-type 83 (SNVT_state[Bit15]), SNVT-No. 5 5 within the device with Neuron-ID 00A051437401     name = binary value written by the gateway. SNVT-type 83 (SNVT_state[Bit15]), SNVT-No. 5 5 within the device with Neuron-ID 00A051437401
Zeile 89: Zeile 91:
  
   Addressing with Domain-ID.Subnet.Node:   Addressing with Domain-ID.Subnet.Node:
-    + 
-    [X object 1]+  [X object 1]
     name = analogue value rerd by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-Nr. 4 within the device with address 01.02.03     name = analogue value rerd by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-Nr. 4 within the device with address 01.02.03
     query = pe     query = pe
Zeile 96: Zeile 98:
  
   Adressing with binding:   Adressing with binding:
-    + 
-    [Y object 1]+  [Y object 1]
     name = Analogue value provided by the gateway. SNVT-Typ 66 (SNVT_volt_f), SNVT-Nr. 2 within the gateway     name = Analogue value provided by the gateway. SNVT-Typ 66 (SNVT_volt_f), SNVT-Nr. 2 within the gateway
     query = pe     query = pe
     format = 66 --- 2     format = 66 --- 2
 +
 +
 +Alternatively you can specify the address formats 'Domain-ID.Subnet.Node' and 'Neuron-ID' directly:
 +
 +  [X 66 000360850201.4]
 +    name = analogue value read by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-No. 4 within a device with Neuron-ID 000360850201
 +    query = pe
 +
 +  [X 105 000360850201.12]
 +    name = analogue value read by the gateway. SNVT-type 105 (SNVT_temp_p), SNVT-No. 12 within a device with Neuron-ID 000360850201
 +    query = pe
 +
 +  [Y 95 00A051437401.4]
 +    name = analogue value written by the gateway. SNVT-type 95 (SNVT_switch[value]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [S 95 00A051437401.4]
 +    name = integer value written by the gateway. SNVT-type 95 (SNVT_switch[state]), SNVT-No. 4 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [M 83 00A051437401.5/1]
 +    name = binary value read by the gateway. SNVT-type 83 (SNVT_state[Bit16]), SNVT-No. 5 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [M 83 00A051437401.5/2]
 +    name = binary value written by the gateway. SNVT-type 83 (SNVT_state[Bit15]), SNVT-No. 5 5 within the device with Neuron-ID 00A051437401
 +    query = pe
 +    writecache = yes
 +
 +  [X 66 01.02.03.4]
 +    name = analogue value rerd by the gateway. SNVT-type 66 (SNVT_volt_f), SNVT-Nr. 4 within the device with address 01.02.03
 +    query = pe
 +
 +  [X 95 00.02.04.32/1]
 +    name = addressing structural element value. SNVT-Typ 95 (SNVT_switch), SNVT-Nr. 32 within the device with address 00.02.04
 +    query = pe
 +
 +  [M 95 00.02.04.32/2]
 +    name = addressing structural element state. SNVT-Typ 95 (SNVT_switch), SNVT-Nr. 32 within the device with address 00.02.04
 +    query = pe
 +
lon_en.txt · Zuletzt geändert: 20.06.2018 07:38 von amu