honeywell_mb100_en
Honeywell MB100
The Honeywell MB100 protocol driver transmits values from alarm panel 561-MB100 via RS-232 or RS-485 interface.
The name of the driver file: hmb
The routing address of the first Honeywell MB100 driver is 1310
The data point list file of the first Honeywell MB100 driver is: hmb1.txt
The configuration file for global settings is: hmb1.cfg
For the Honeywell MB100 driver as well as all other drivers following definitions in the data point file lists are valid:
Type | Description |
---|---|
M | Integer value (binary data points, counters) which can/shall only be read by the gateway |
S | Integer value which can be either read or written by the gateway. (to M-BUS writing is not possible) |
X | Floating point value (with decimal place) which can/shall only be read by the gateway |
Y | Floating point value (with decimal place) which can be either read or written by the gateway. (to M-BUS writing is not possible) |
A | String, is used e.g. with BACnet Trends and ESPA4.4.4 data points |
Addresses are defined as follows: „<type> <number>.<state>“
Followinf definition is valid:
Parameter | Range | Description |
---|---|---|
<type> | event, command | Message from panel Message to panel |
<number> | Integer | sensor's address (–> see documentation of the manufacturer). |
<state> | Integer | sensor's state /control function for event/command (–> see documentation of the manufacturer). |
The alarm state for main area 1 is defined in file hmbX.txt as follows:
[M event 72.0]
The command switch for main area 1 is defined in file hmbX.txt as follows:
[S command 72.0]