Benutzer-Werkzeuge

Webseiten-Werkzeuge


eib_knx_en

EIB/KNX

The EIB/KNX driver allows reading, writing, and creating KNX data points. The driver can either access existing data points as well as provide own local data points on the gateways itself.

For gateways with an integrated KNX interface, setting the physical address (per default 15.15.255) to any allowed address can be accomplished using the webfrontend.

In order to achieve current values for all data points after booting the gateway it is necessary to set the reading-flag on the ETS side.

Otherwise the data points will be transmitted to the gateway only after change of value and the gateway's booting process delays. The gateway retries unsuccessful reads several times. In case a data point cannot set the reading-flag a dedicated option can be used which indicates the driver to skip the reading of this value during boot-up.

Please not that for operating a KNX network an external KNX-power supply is required.

Normally such a power supply is already available in existing KNX networks.n KNX Netzen vorhanden.

The EIB/KNX- driver's name is: eib
The routing-address of the first EIB/KNX driver is 70
The configuration file for the first EIB/KNX driver is: eib1.txt
The configuration file for global settings of the first EIB/KNX driver is: eib1.cfg

In case gateway models UGW-Compact or UGW-Maxi with Tapko UIM-42 KNX-USB connector are used then a different driver is necessary. The syntax regarding data point definitions is identical .However name and routing-address are different.

The name of the EIB/KNX-USB driver is : eibusb
The routing address of the first EIB/KNX-USB driver is 1130
The configuration file for the first EIB/KNX driver is: eibusb1.txt
The configuration file for global settings of the first EIB/KNX-USB driver is: eibusb1.cfg

For the EIB/KNX driver as well as all the other gateway driver the definition of data points is as follows:

Type Description
M Integer value (binary data points, counters) which can/shall only be read by the gateway
S Integer value which can be either read or written by the gateway. (to M-BUS writing is not possible)
X Floating point value (with decimal place) which can/shall only be read by the gateway
Y Floating point value (with decimal place) which can be either read or written by the gateway. (to M-BUS writing is not possible)
A String, findet z.B. Verwendung bei BACnet Trends und ESPA4.4.4 Datenpunkten

The driver can either process 2-digit as well as 3-digit KNX addresses. Addresses are definied as follows:

2-digit: „<maj>.<min>„
3-digit: “<maj>.<mid>.<ext>„
communication state with EIB: „failure“

While following definitions are valid:

Parameter Range of value Description
<maj> 0-31 upper group address
<min> 0-2047 lower group address
<mid> 0-7 middle group address
<ext> 0-255 extended group address

The address of a binary source data point with the 3-digit address will be defined in the file eibX.txt or eibusbX.txt like this:

[M 5.3.10]

In order to interpret the data of the address properly it is necessary to give format definitions for each data point. Below please find the available format options.

format = <format> [F:<fact>] [P:<poll>][U:<upd>] [I:<opt>] [L:<loc>] [H:<prio>] [R:<addr>] [D:<dly>]

possible <format> definitions you can find in the table below.

<format> Description
UINT1 1bit
UINT2 2bits
UINT3 3bits
UINT4 4bits
UINT5 5bits
UINT6 6bits
UINT7 7bits
UINT8 8bit unsigned
SINT8 8bit signed
UINT16 16bit unsigned
SINT16 16bit signed
UINT24 24bit unsigned
UINT32 32bit unsigned
SINT32 32bit signed
FLOAT 32bit IEEE754 floating point
DOUBLE 64bit IEEE754 floating point
SFLOAT 16bit IEEE754 floating point

Table of EIB/KNX standard data types and associated UGW Format:

EIS Typ DPT Typ Länge Bedeutung UGW Format
EIS-1 DPT-1 1 Bit Schalten UINT1
EIS-2 DPT-3 4 Bit Dimmen UINT4
EIS-3 DPT-10 3 Byte Zeit UINT24
EIS-4 DPT-11 3 Byte Datum UINT24
EIS-5 DPT-9 2 Byte Fliesskomma kurz SFLOAT
EIS-6 DPT-5 DPT-6 1 Byte Relativwert UINT8 F:2.55
EIS-7 DPT-1 1 Bit Antriebssteuerung BIT1
EIS-8 DPT-2 1/2 Bit Prioritätskontrolle UINT1 / UINT2
EIS-9 DPT-14 4 Byte Fliesskomma IEEE754 32Bit FLOAT
EIS-10 DPT-7 DPT-8 2 Byte Zähler 16Bit UINT16 / SINT16
EIS-11 DPT-12 DPT-13 4 Byte Zähler 32Bit UINT32 / SINT32
EIS-12 DPT-15 4 Byte Zuganskontrolle UINT32
EIS-13 DPT-4 1 Byte ASCII/ISO8859-1 Zeichen UINT8
EIS-14 DPT-5 DPT-6 1 Byte Zähler 8Bit UINT8 / SINT8
EIS-15 DPT-16 14 Byte Text 14 Zeichen
8 Byte Fliesskomma IEEE 64Bit DOUBLE
DPT-17 1 Byte Szene UINT8
DPT-20 1 Byte HVAC Mode UINT8
DPT-21 1 Byte Status UINT8
DPT-22 2 Byte Status UINT16
DPT-23 2 Bit Action on/off Alarm up/down UINT2
DPT-25 1 Byte Double Nibble UINT8
DPT-26 1 Byte Scene Info UINT8
DPT-27 4 Byte combined info on/off UINT32
DPT-232 3 Byte RGB Farbwert UINT24

If required the format definition can be extended with more parameters. Please find descriptions in the table below.

Value Range of values Description
F:<fact> valid 32Bit floating point value The value transmitted by the KNX-Bus is divided by <fact>. Values sent to the KNX-bus will be multiplied by <fact>. Default for <fact> is 1.0
P:<poll> 0 - 216 Interval in seconds between two active polls of a data point. Default for <poll> is „0“. That means no cyclic reading.
U:<upd> 0 - 216 Interval in seconds between two active writes to the data point. Default for <upd> is „0“. That means no cyclic writing.
I:<opt> 0 - 7 Bit0 change of value:
„0“ filter changes
„1“ do not filter changes
Bit1 poll value:
„0“ generate reading
„1“ do not generate reading
Bit2 local writing:
„0“ do not generate local writing request
„1“ generate writing request
default <opt>-flag is „0“.
Remark: For local data points Bit0 and Bit1 are static „1“
L:<loc> 0 - 1 „0“ remote data point
„1“ local data point
H:<prio> 0 - 1 „0“ low priority (default)
„1“ high priority
Defines the order in which the data points are processed by the gateway. data points with high priority are processed before low priority data points.
R:<addr> valid EIB data point, „failure“ excluded This address will be read after the data point referring to this option has been updated.
D:<dly> 0 - 216 The driver delays the reading request (see R:<addr>) for <dly> seconds. Default for <dyl> is „0“

typical definitions of data points:

[M 5/3/10]
 name = digital operation message
 query = pe
 format = UINT1
[S 2/10]
 name = digitale given value
 query = pe
 format = UINT1
 writecache = yes
[M 5/3/11]
 name = multistate message e.g. 0, 1, 2 for Off, On, Auto
 query = pe
 format = UINT8
[S 5/3/12]
 name = multistate given value e.g. step switch 0,1,2 for Off, On, Auto
 query = pe
 format = UINT8
 writecache = yes
[X 5/3/13]
 name = temperature value
 query = pe
 format = SFLOAT
[Y 5/3/14]
 name = temperature given value
 query = pe
 format = SFLOAT
 writecache = yes

per cent values 0-100% in EIB/KNX are often scaled 0-255. Therefore it is necessary to divide the value by 2.55.

[X 5/3/15]
 name =  percentage
 query = pe
 format = UINT8 F:2.55
# fixed point value (16 Bit, with factor 10)
[X 13/3/222]
 name =  fixed point value
 query = pe
 format = UINT16 F:10
eib_knx_en.txt · Zuletzt geändert: 17.07.2017 16:56 von Jochen Erwied