 +<​code>​
 +# Configuration file for EIB driver
 +#
 +# Section: EIB
 +#
 +# Entries:
 +#
 +# Name          Type    Range               ​Description
 +#
 +#   ​Baudrate ​   int     ​38400, ​             Communication speed.
 +#                       ​19200,​\n"​
 +#                       9600 (default)\n"​
 +#   ​QueueSize ​  ​int ​    ​1..10000 ​           DPmngr queue size.
 +#   ​ForceAuto ​  ​int ​    0 - disabled ​       Force '​Auto'​ flag for
 +#                       1 - enabled ​        ​nominal datapoints
 +#   ​MonitorMode int     0 - disabled ​       Bus monitor mode.
 +#                       1 - enabled
 +#   ​AliveCheck ​ int     0 - disabled ​       Number of seconds without
 +#                       ​1..3600 ​            data exchange that trigger a
 +#                                           BCU alive check.
 +#   ​BcuType ​    ​int ​    ​0..2 ​               0 normal BCU (default)
 +#                                           1 siemens TP-UART-2
 +#                                           2 nxp NCN5120 TP-UART
 +#   ​PhysicalAddress string high.mid.low ​    ​Phyiscal address of interface
 +#                       high = 0..15
 +#                       ​mid ​ = 0..15
 +#                       ​low ​ = 0..255 ​      ​Default:​ 15.15.255 ​
 +#                          ​
 +#
 +#
 +# Section: TARGET<​no>​ (<no> - target number, 1..64)
 +#
 +# Entries:
 +#
 +# Name          Type    Range               ​Description
 +#
 +# Entry<​no> ​    ​string ​ <​adr>​[,<​adr>​...] ​   The list of data point addresses
 +#
 +# where:
 +#   <​no> ​   - the entry number (1..64)
 +#   <​adr> ​  - the data point address (EIB format)
 +#
 +#
 +# Section: DISPATCH
 +#
 +# Entries:
 +#
 +# Name          Type    Range               ​Description
 +#
 +# Source ​       string ​ <​adr> ​              The address of the data point to
 +#                                           be dispatched
 +# Target ​       string ​ <​no>​[,<​no>​...] ​     The list of target numbers to
 +#                                           ​dispatch to
 +#
 +# where:
 +#   <​adr> ​  - the data point address (EIB format)
 +#   <​no> ​   - the target number (1..64)
 +
 +[EIB]
 +Baudrate ​   = 38400
 +Queuesize ​  = 2000
 +ForceAuto ​  = 0
 +MonitorMode = 0
 +AliveCheck ​ = 0
 +BcuType ​    = 2
 +PhysicalAddress = 15.15.255
 +
 +# [TARGET1]
 +# Name    = Target1
 +# Entry1 ​ = 1/0/0, 1/0/1, 1/0/2
 +# Entry2 ​ = 1/0/3, 1/0/4, 1/0/5
 +
 +# [TARGET2]
 +# Name    = Target2
 +# Entry1 ​ = 2/1/1, 2/1/2, 2/1/3
 +
 +# [DISPATCH]
 +# Source ​ = 1/0
 +# Target ​ = 1
 +
 +# [DISPATCH]
 +# Source ​ = 2/0
 +# Target ​ = 2
 +
 +# [DISPATCH]
 +# Source ​ = 3/1/1
 +# Target ​ = 1, 2
 +
 +</​code>​
  